Outdoor Online UPS

Application field

Tis UPS is commonly used in the corner of the city,remotr roads,mountains,bad environment,such as high temperature (

±50)/low temperature (-40),servere dust,moisture,rain,misterosion,very poor power quality(voltage longterm higher than 260V or less than 160V,frequency abnormal change)in the area.

Main parameters

Model 1KVA 2KVA 3KVA 6KVA 10KVA
Range voltage 220/230/240VAC
Frequency 50Hz/62Hz
Input
Voltage range 115~295VAC(±3VAC) 176~297VAC(±3VAC)
Frequency Range 50Hz (46~54 Hz) ; 60Hz (56~64 Hz)
Soft Start 0~100% 5sec
Power factor 0.98
Output
Voltage Precision 220/230/240VAC(1±2%)AC
Frequency Precision 50Hz/62Hz±0.05Hz
Power factor 0.7/0.8(optional) standard 0.7
Wave Distortion Linear load<3% Non-linear load<6%
Overload capability Overload(110~150%)for 30 seconds,then automatically transfer to bypass.When load is normal,it can automatically transfer to normal mode
Crest Factor 3:1
Transfer time 0ms (AC to DC)
battery 36VDC 72VDC 96VDC 240VDC 240VDC
Charging current 4A/8A(optional) 4A/8A(optional) 4A/8A(optional) 4.2A 4.2A
Internal Battery Caoacity (38/65/80/100AH) optional
Panel display
LED Load level/Battery level ,Battery indicator,Utility power,Inverter ,Bypass,Overload ,Fault
Communications
Communications interface RS232 SNMP card(optional)
Work Environment
Temperature -40~55ºC
Humidity 0~95%(Non-condensing
Storage Temperature -25ºC~55ºC
Elevation <1500m
Physical Characteristics
Weight(KG)N.W 85 125 125 150 150
Dimensions:(WxDxH)mm 613*640*954 650*753*1227 650*753*1227 940*940*1770 940*940*17

Features

Feature:
  • Consnant Outdoor Intelligent High Frequency Online UPS provide continuous pure sine wave AC power supply for outside communications / network equipment.
  • Double-conversion online design, high temperature resistant, anti-cold, sealing level for IP55; 
  • With the wide range of input voltage and frequency of input window (-45% +35% rated voltage and ± 10% rated frequency), in many remote areas of China after a severe test of the grid.
  • With a sun protection, heat insulation, roof ventilation
  • With waterproof and the filtration dust inlet
  • The cabinet front door shutters with waterproof design, on the back of welding water tank, water tank installed above the net with quick release feature of the dust.