Main Features
1.1 Summarization
Our UPS is a kind of three-in- three -out high frequency online UPS, it provides three specifications: The 200~600kVA. The products are modularized and adopt the N+X redundancy. It can flexibly increase the number of the UPS modules according to the load capacity which is convenient for flexible allocation and gradually investment.
The UPS can solve most of the power supply problems, such as blackout, over-voltage, under-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage fluctuation, surge, inrush current, harmonic distortion (THD), noise interference, frequency fluctuation, etc..
This UPS can be applied to different applications from computer device, automatic equipment, communication system to industry equipment
1.2 Functions and Features
◆Digital control
◆19-inch standard cabinet
2-meter high cabinets are provided according to the user’s requirement.
◆Modularized design
◆High power-density design
The height of the single module is 3U.
◆N+X parallel redundancy
This series UPS adopts N+X parallel redundancy design, user can set different redundancy according to the importance of the load. While the redundancy modules are set more than two, the availability of UPS system will achieve 99.999%, which may satisfy the required reliability of the critical load connected. Through LCD display setting, you may configure the required quantity of the redundancy unit. When the load connected is over the number of the redundancy, the UPS will alert right away. The design of the MTBF (Meantime before Failure) is up to 250,000 hours.
This series can set the number of redundancy modules. When the load exceeds the redundancy setting, the UPS can still work normally and simultaneously send out corresponding warning as long as the load doesn’t exceed the total capacity of modules.
◆Parallel redundant control system
◆Optimizing distributed convergence for the cabinet
◆Centralized bypass
◆Common Battery
◆Automatic charge current adjustment according to battery capacity connected.
◆3-Stage Intelligent charging
◆Touch-screen Super-large LCD display
◆Remote monitoring via SNMP
◆Optional Accessories available such as Isolation transformer, distribution Panel, SNMP Card,
Relay Contact Board, etc...
◆Equip with Maintenance Bypass Switch for easy maintenance purpose.
◆Superior MTTR (Meantime to repair) & Short shutdown time in maintenance
◆Centralized monitoring module is also available
◆EPO and REPO function
1.3 Model description
This document describes the following UPS models:
◆ 200kVA
The models provide 4 configurations: 50 kVA, 100 kVA, 150 kVA and 200 kVA
◆ 300kVA
The models provide 6 configurations: 50 kVA, 100 kVA, 150 kVA, 200 kVA, 250 kVA and 300 kVA.
◆ 400kVA
The models provide 8 configurations: 50 kVA, 100 kVA, 150 kVA, 200 kVA, 250 kVA, 300 kVA, 350 kVA and 400 kVA.
◆ 500kVA
The models provide 10 configurations: 50 kVA, 100 kVA, 150 kVA, 200 kVA, 250 kVA, 300 kVA, 350 kVA, 400 kVA, 450 kVA and 400 kVA.
◆ 600kVA
The models provide 12 configurations: 50 kVA, 100 kVA, 150 kVA, 200 kVA, 250 kVA, 300 kVA, 350 kVA, 400 kVA, 450 kVA, 500 kVA, 550 kVA and 400 kVA.
◆ 200kVA supports cable routing from the top and can support cable routing
◆ 300kVA supports cable routing from the top and can support cable routing
from the bottom if a cable entry cabinet is configured.
◆ 400kVA standard cabinet supports cable routing from the top.
◆ 400kVA full configuration cabinet supports cable routing from the bottom and top.
◆ 500kVA supports cable routing from the bottom and top.
◆ 600kVA supports cable routing from the bottom and top.
* Standard configuration : cabinet only with maintenance bypass switch
* Full configuration : cabinet with mains, bypass, maintenance and output switch
The appearance of the product
200/300/400kVA(Standard and Full configuration)
Front View Side View Rear View
200kVA(Standard and Full configuration)
300kVA(Standard and Full configuration)
400kVA (Standard configuration)
400/500/600kVA (Standard and Full configuration)
400kVA (Full configuration)
500kVA(Standard and Full configuration)
600kVA (Standard and Full configuration)
(1) LCD panel : Display UPS data and status
(2) power cabinet : Assembly power module
(3) Power distribution cabinet : Assembly control unit, bypass module and switch
(4) Power module
(5) Control unit
(6) Mains switch
(7) Output switch
(8) Maintenance switch
(9) Bypass switch
(10) Bypass module
(11) Mains-A input copper bar
(12) Mains-B input copper bar
(13) Mains-C input copper bar
(14) Input neutral copper bar
(15) Battery negative copper bar
(16) Battery neutral copper bar
(17) Battery positive copper bar
(18) Output-A input copper bar
(19) Output-B input copper bar
(20) Output-C input copper bar
(21) Output neutral copper bar
(22) Bypass-A input copper bar : Wiring must be used when mains-bypass separation
(23) Bypass-B input copper bar : Wiring must be used when mains-bypass separation
(24) Bypass-C input copper bar : Wiring must be used when mains-bypass separation
(25) Phase A mains-bypass common input connect copper bar
(26) Phase B mains-bypass common input connect copper bar
(27) Phase C mains-bypass common input connect copper bar
Control unit
(1) ECU1/2 : Centralized control unit
(2) Dry-contact unit
(3) monitor unit
(4) Intelligent slot
ECU unit
(1) EPO port
(2) SWITCH STATUS
(3) the other port
(4) BP_FEEDBACK : PIN1_NC, PIN2_NO,PIN4_common
(5) Optional dry contacts
Monitor unit
(1) Input dry contacts
(2) LCD port
(3) CAN port : BMS port and remote LCD port
(4) COM : battery monitor port
(5) BAT_T : battery temperature detect port
(6) PE
(7) RS-485
UPS module appearance
Front View
Side View
(1) Module fixed screw
(2) LED
(3) Module switch
(4) Fan
Model
300kVA
400kVA
500kVA
600kVA
Cabinet capacity (VA/W)
50k~300k/50k~300k
50k~400k/50k~400k
50k~500k/50k~500k
50k~600k/50k~600k
Module capacity (VA/W)
50k/50k
Max. module number
6
8
10
12
Input
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Voltage Range
38~485Vac
◆ At 40°C: The UPS works at ful l load when the voltage is 323–485Vac and is derated load when the voltage is 323–138Vac
◆ At 30°C: The UPS works at ful l load when the voltage is 305–485Vac and is derated load when the voltage is 305–138Vac
Frequency Range
40Hz-70Hz
Power Factor
≥0.99
Current THDi
≤3%(100% nonlinear load)
Bypass Voltage Range
Max.voltage: 220V:+25 %( optional +10%, +15%, +20%);
230V:+20 %( optional +10%, +15%);
240V:+15 %( optional +10%);
Min. voltage:-45 %( optional -10%, -20%,-30%)
Frequency protection range: ±10%
Output
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Power Factor
1
Voltage Regulation
±1%
Frequency Range
Utility Mode
±1%/±2%/±4%/±5%/±10%of the rated frequency(optional)
Battery Mode
(50/60±0.1)Hz
Crest factor
3:1
THD
≤2% with l inear load
≤4% with non l inear load
Overload
Optional Voltage:
±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc
(30/32/34/36/38/40/42/44/46/48/50pcs optional)
384Vdc~480Vdc
(30~40 pcs, 40 pcs define, 36 and 50 pcs no power derating; 32~34 pcs output power factor
Battery
Voltage
Optional Voltage:
±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc
(30/32/34/36/38/40/42/44/46/48/50pcs optional)
384Vdc~480Vdc
(30~40 pcs, 40 pcs define, 36 and 50 pcs no power derating; 32~34 pcs output power factor
Module charge current (A) max.
20A
Transfer Time
Utility to Battery : 0ms; Utility to bypass: 0ms
Protection
Short Circuit
Hold Whole System
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Battery Low
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
EPO
Shut down UPS immediately
Battery
Advanced Battery Management
Noise Suppression
Complies with EN62040-2
Communication Interface
CAN, RS485, FE, LBS, Parallel, Relay card, SNMP card(optional)
Environment
Operating Temperature
0℃~40℃
Storage Temperature
-25℃~55℃
Humidity
0~95% non condensing
Altitude
< 1500m
Display
Audible & Visual
Line Failure, Battery Low, Overload, System Fault
Status LED
UPS Fault, Alarm and normal
Reading On the LCD
Input Voltage, Input Frequency, Output Voltage, Output Frequency,
Load Percentage, Battery Voltage, parameter set, history record…
Other
Standard cabinet Dimensions (W*D*H)
600*850*2000
600*850*2000
1200*850*2000
Full cabinet Dimensions(W*D*H)(mm)
1200*850*2000
Module Dimensions(W*D*H)(mm)
440*620*130
Cabinet Weight (Kg)
260
280/600
650
720
Module Weight (Kg)
34
Safety Conformance
CE,EN/IEC 62040-3,EN/IEC