Model |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
Capacity |
8KW |
12KW |
16KW |
24KW |
32KW |
Input |
Rated voltage |
380/400/415 Vac three-phase |
Voltage range |
±20% |
Frequency range |
45-65Hz |
Power factor |
>0.92 with harmonic filter |
Current harmonic distortion |
<5% with harmonic filter |
Soft Start |
0 -100% in 10″ |
Bypass Input |
Rated voltage |
230Vac single-phase |
Permitted voltage range |
±15%(selectable from ±10% to ±25% from front panel) |
Rated frequency |
50/60Hz |
Permitted frequency range |
±2%(selectable from ±1% to ±5% from front panel) |
Standard features |
BackFeed portection; split bypass line |
Batteries |
Type |
Maintenance-free lead-acid VRLA AGM / GEL;NICd |
Battery Voltage |
384VDC |
Maximum recharge current(A) |
0.2 X C10 |
AC ripple voltage |
<1% |
Inverter output |
Rated power(kVA) |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
Active power(kW) |
8KW |
12KW |
16KW |
24KW |
32KW |
Number of phases |
1 |
Rated voltage(V) |
230Vac single-phase |
Regulation of the output voltage |
220 ~ 244Vac phase/neutral(from control panel) |
Crest factor(Ipeak/Irms) |
3:1 |
Static stability |
±1% |
Dynamic stability |
±5% |
Frequency |
50/60Hz configurable |
Overload |
110% 125% 150% of the rated current for 5h/10’/1′ |
Frequency stability |
±0.05% on mains failure |
System |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
Remote signaling |
Volt free contacts |
Remote controls |
EPO and Bypass |
Communication |
RS232 + romote contacts |
Operation temperature |
0℃ to + 40℃ |
Relative humidity |
<95% non condensing |
Colour |
Light grey (RAL 7035) |
Noise |
54dBA at 1m |
60dBA at 1m |
65dBA at 1m |
Protection degree |
IP20 |
Efficiency Smart Mode |
up to 98% |
Compliance |
Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC) |
Weight(KG)N.W |
176 |
220 |
205 |
213 |
295 |
Dimensions:(WxDxH)mm |
555*730*1210 |
Internal batteries |
optional |
optional |
optional |
No |
No |
Features
High intelligence and reliable power supply:
It provides maximum protection for vital mission-critical networks, security applications (electro-medical), and industrial applications thanks to its outstanding mechanical and electrical design.
The load is powered continuously by the inverter with a filtered, stabilized, and regulated sine wave supply. The input and output EMI filter considerably increase the immunity of the load to mains disturbances and surges.
The CNG330 series UPS uses on-line double conversion technology (VFI) with an isolation transformer on the inverter output.
It is supplied with Watch & Save 3000 software as standard and can be remotely monitored
using the Power Net Guard system from anywhere in the world. Additional battery extension packs allow the standard battery routine to be extended up to several hours.
Minimum impact on supplies easy sources:
Input current distortion <4% for the CNG330 with a filter with sinusoidal absorption to remove the risk of resonance with other input supply users or phase shift capacitor sets. The absorbed current distortion is independent of input supply parameters such as impedance. This enables CNG330 to deliver maximum performance levels regardless of the installation environment. With these input features CNG330 can achieve significant savings in terms of sizing and power supply sources isolation transformers and generators over less sophisticated power systems.
Maximum battery care:
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
Simple to install:
Capability to install the UPS into any distribution system(neutral not required on rectifier input);
Capability to separate the rectifier/bypass power networks and to power these from two separate sources, without Galvanic isolation (Necessary on UPS without an output transformer).
High reliability:
Extremely high short-circuit current to ensure compatibility with the most difficult transformer applications (lighting, drives, and industrial processes) and an isolation transformer on the inverter output;
Full microprocessor control with no-break static and manual bypasses;
IGBT technology.
Other characteristics
0.8 power factor make CNG330 suitable for powering ICT and Industrial loads;
High-level diagnostics: event log with 128 messages, states, measurements, and alarms – available from the built-in LCD with several languages;
Back feed protection: to avoid energy feeding back into the mains supply cause a fault to occur.
Maximum reliability and availability
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings. The UPS continues to work in parallel even if one of the interconnecting communication cables is disconnected (CLOSED LOOP).
Low consumption level:
CNG330 can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
Advanced communication
Compatible with TeleNetGuard for remote maintenance;
Advanced, multi-platform communication for all operating systems and network environments: Watch & Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows 2008, Vista,2003, XP; Mac OS X, Linux, Novell, and most popular Unix operating systems;
The UPS is supplied with a cable for direct connection to the PC(Plug and Play);
RS232 double Serial port; Installation slot for an Emergency Power Off (EPO) interface to allow the UPS to be switched off remotely in an emergency;
Generator interface: enables desynchronization of the UPS output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charge.
Expandability:
The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single
module or the system can be expanded at any time to suit power requirements without influencing the initial investment.