working principles
1. External current transformer(CT)could detect real-time load current .
2. Internal DSP calculates and analyzes the reactive power content of the system.
3. Control PWM to send signal to IGBT to generate reactive power compensation current for power factor compensation.
Electrical Features& Specifications
Item
Description
Main Function
Harmonic Filter
Setting filtering from 2-51 times(under only harmonic filtering function)
While choose priority, the harmonic filtering is 2-13th
Auto/Priority function
The user can also set the priority function, including H+Q/ Q+H/Q+H+B/H+Q+B (Q power factor, H harmonic filtering, B, unblance )ref:Tab.4-1
Application
Hotel,Car park, Car charger station,Car 4S store,IDC, hospital,Railway,water treatment and other non-liner load
Electrical
Rated voltage
380/400Vac or 690Vac
Wiring
3P3W or 3P4W
Frequency
50±2Hz
Capacity
20~100A(According to SVG type)
Module Consumption
<2kW
Efficiency
Up to 97.5%
switching frequency
20kHz
Response time
Fast response time<50μs
Total response time<5ms
CT ratio
150:5~6000:5
Parallel
Max.5 (customization acceptable)
Terminals
Communication
RS485
Environment
Operating environment
In-door, free from moisture, dust, corrodent or flammable gases, oil mist, vapor, water leakage or salt water.
Altitude
<1000m (customized acceptable)
Work temperature
-20℃~+50℃( derating is required from 40℃ to 50℃, increase every 1℃ above 40℃, derating 2%, highest temperature allowed: 50℃ )
Humidity
Less than 95%RH, no condensing
Storage temperature
-20℃~+70℃
Vibration
Less than 5.9m/s2 (0.6g)
Enclosure
Protection degree
IP20
Colour
7035 grey (customization acceptable)
Size
According to APF type(refer: APF Dimensions)
Cooling
Fan cooling