Model:CNME331 60-120K
Capacity: 60-150KVA
Input Voltage Range:138~485Vac
Output Rated Voltage:380/400/415Vac
Application:
Data centers; Small server room, Network, Bank, Security, Transportation, Broadcast&TV network, HealthCare, Communication, Finance,Small and medium-sized substations and power plants; Production process control in manufacturing and petrochemical industries, etc.
Item No :
CNME331 60-120KOrder(MOQ) :
1 pcsPayment :
T/TProduct Origin :
ChinaColor :
BlackShipping Port :
ShenzhenLead Time :
2-3 weeksWeight :
60 - 180 Kg
CNME331 series UPS is an embedded modular UPS of low and medium power developed by CONSNANT. The core power unit of this UPS adopts a modular prefabricated design, with all modules being hot-swappable online, making online maintenance and capacity expansion more convenient and efficient.
Technical Parameters:
| Model | CNME331-60K CNME331-80K CNME331-120K |
CNME331-120K | ||||
| Capacity | Frame | 10~120kVA | 25~150kVA | |||
| Module | 10/15/20kVA | 25/30kVA | ||||
| Max. Module Number | 2/4/6 | 6 | ||||
| Input | Phase | 3 Phase 4 Wires and Ground | ||||
| Rated Voltage | 380/400/415Vac | |||||
| Voltage Range | 138~485Vac | |||||
| Frequency Range | 40Hz-70Hz | |||||
| Power Factor | ≥0.99 | |||||
| Current THDi | ≤3%(100% linear load) ; ≤5%(100% non-linear load) | |||||
| Bypass Voltage Range | Max.voltage: 220V:+25 %( optional +10%, +15%, +20%); 230V:+20 % ( optional +10%, +15%); 240V:+15 %( optional +10%); Min. voltage: -45% (optional -20%、-30%) |
|||||
| Frequency protection range: ±10% | ||||||
| Generator access | Yes | |||||
| Output | Phase | 3 Phase 4 Wires and Ground | ||||
| Rated Voltage | 380/400/415Vac | |||||
| Power Factor | 1 | |||||
| Voltage Regulation | ±1% | |||||
| Frequency | Utility Mode | ±1%,±2%,±4%,±5%,±10% of the rated frequency(optional) | ||||
| Battery Mode | (50/60±0.1%)Hz | |||||
| Crest Factor | 3:1 | |||||
| THD | ≤2% with linear load; ≤4% with non linear load | |||||
| Efficiency | 95.5% | |||||
| Overload | ≤ 110%: to bypass after 60 min, ≤ 125%: to bypass after 10 min, ≤ 150%: to bypass after 1 min |
|||||
| Battery | Voltage | ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional) |
||||
| Charging Current | UPS Cabinet | 2 layer cabinet:20A Max. / 4 layer cabinet:40A Max. 6 layer cabinet:60A Max. |
||||
| UPS Module | 5A Max. | 10A Max. | ||||
| Transfer Time | Utility to Battery : 0ms; Utility to bypass: 0ms | |||||
| Protection | Alarm | overload, utility abnormal, UPS fault, battery low, etc | ||||
| Protection | short circuit, overload, over temperature, battery low, fan fault alarm | |||||
| Communication Interface | USB, CAN, RS485, FE, Parallel card, Dry contact card, SNMP card(optional), LBS(optional ),temperature sensor (optional) | |||||
| Environment | Operating Temperature | 0℃~40℃ | ||||
| Storage Temperature | -25℃~55℃ (no battery) | |||||
| Humidity | 0~95% (non condensing) | |||||
| Altitude | < 1500m | |||||
| Noise level | <70dB | |||||
| Other | Unit Dimensions(D*W*H) mm | Frame | 2 layer:750*485*650/ 4 layer:750*485*827 / 6 layer:850*485*1005 | |||
| Module | 620x440x86 | |||||
| Net Weight (kg) | Frame | 63/75/87 | ||||
| Module | 10/15/20K:19 25/30K:21.6 |
|||||
| Standards | EN62040-1, EN62040-2,EN62040-3 | |||||